VA-P2120/
VA-P2240/ VA-P2350/ VA-P2500 Digital Amplifier
Learn more
Descriptions:
VA-6100MA Controller is the core management and control equipment for building public broadcasting and fire emergency broadcasting. It uses a 5- inch high-definition touch screen to directly complete system control and status query. The system function configuration and control can also be performed through PC management software. It can automatically complete the monitoring and management of the system physical partition status, automatically complete the monitoring and management of terminal equipment, and automatically execute user pre-programmed control, etc.; the built-in programmable trigger input and output interface is used to realize interoperation control with the sound and light alarm module (it can also be connected to the bus-based fire linkage controller ) .
| AC power input voltage | ~ 220V ± 15 % , 50Hz - 60Hz |
|---|---|
| AC power input current | Less than 0.5A |
| DC power input voltage | DC24V , 19-30V adaptive |
| DC power input current | 2A |
| Fuse specifications | 250V/1A, slow type |
| Maximum power consumption of the device | 44 W |
| Emergency microphone sensitivity | 10mV |
| Emergency microphone impedance | 600Ω |
| Line input number | 5 channels (1 channel Kalon interface, 4 channels RCA interface) |
| Line input sensitivity | ± 385mV (balanced), 775mV (unbalanced), 10mV (unbalanced) |
| Line input impedance | 20KΩ (balanced), 10KΩ (unbalanced) |
| Recording output channels | 1 channel (1 RCA interface) |
| Recording output distortion | <1% |
| Recording output amplitude | 200mV |
| Recording output frequency response | 200Hz- 16k Hz |
| Recording output signal-to-noise ratio | > 70 dB |
| Programmable output for system fault | Short circuit , no voltage |
| Fire linkage programmable output | Short circuit , no voltage |
| 8-channel relay programmable output | Short circuit, no voltage |
| Programmable DC24V power output | DC24V , 0.3A |
| Programmable input trigger types | Short-circuit input, short-circuit input with detection |
| Short circuit mode | 3.3V voltage, short contact trigger, no linkage line monitoring function |
| Short-circuit mode with detection | 3.3V voltage, short contact trigger, support linkage line fault alarm |
| Fire reset input | Contact ≥0.5S , no voltage |
| Voice message data format | MP3 or WMA format |
| Voice information storage type | TF card |
| Dimensions ( L×D×H ) | 484×4 77 . 7 × 100.5 mm |
| Weight | About 7kg |