Home / Products / EN54 — Voice Evacuation / VA-6100MS

VA-6100MS

8 Channel Changeover

VA-6100MS
EN54 — Voice Evacuation · 6100 Series

Descriptions:

VA-6100MS changeover integrates the main and standby power amplifier conversion functions, ground detection, open circuit detection, and short circuit detection of the speaker circuit. It is also compatible with three-wire and four-wire volume controller wiring. It does not require additional wiring and power supply, and has 8-channel programmable dry or wet node trigger inputs and 8-channel programmable online output signals. The controller can be combined with Class D digital amplifiers and traditional analog amplifiers to build a user audio amplification system, providing a safe, stable, and economical solution for the system.

Features

  • It adopts 2U chassis with highly integrated and modular design.
  • Supports real-time detection of speaker loop grounding, open circuit and short circuit, and automatic protection of the amplifier in case of short circuit fault.
  • Supports 3/4-wire speaker loop wiring, fire alarm broadcasting, audio control and forced cutting, and maximum volume output.
  • It has 8 programmable trigger input online interfaces, which can trigger the pre-programmed voice messages to the specified partitions.
  • It has 8 programmable trigger output online interfaces, which can output short-circuit voltage-free relay control signals to third-party equipment to achieve online automatic control.
  • Supports the amplifier to enter power saving mode when there is no signal input to save energy.
  • Supports connection with linkage fire alarm controller to realize fire alarm linkage control.
  • Provides a DC 24V backup power input interface (24V DC power provided by an external DC power charger) to realize main and backup power supply.

Request a quote for this product

Technical specifications

AC power input voltage ~ 220V ± 15 % , 50-60Hz
AC power input current < 1 A ( including 4-wire forced output )
DC power input voltage DC24V , 19-30V adaptive
DC power input current < 6.25 A
Maximum power consumption 150W
Number of output partitions Up to 8
Output voltage 100V
Output type Transformer-less bridge-tied output
Output power 500W ( maximum output of a single zone )
Maximum output power 8×500W
Strong cutting type 3-wire and 4-wire
4-wire forced output voltage 24V
Amplifier status detection time < 1 S
Partition detection status Short circuit, open circuit, short circuit to ground
Partition detection time < 1 S
Line input number 8-way
Line input sensitivity ± 385mV (balanced)
Line input impedance 20KΩ
8-channel relay programmable output Short circuit, no voltage
8-channel programmable trigger inputs Short-circuit input, short-circuit input with detection, voltage input
Short circuit mode 3.3V voltage, short contact trigger, no linkage line monitoring function
Short-circuit mode with detection 3.3V voltage, short contact trigger, support linkage line fault alarm
Cooling method Air-cooled
Dimensions (L x D x H) 484×4 65.1 × 100.5 mm
Weight About 7.3kg